Littelfuse products are not designed for, and shall not be used for, any purpose (including, without limitation, automotive, military, aerospace, medical, life-saving, life-sustaining or nuclear facility applications, devices intended for surgical implant into the body, or any other application in which the failure or lack of desired operation of the product may result in personal injury, death, or property damage) other than those expressly set forth in applicable Littelfuse product documentation. Warranties granted by Littelfuse shall be deemed void for products used for any purpose not expressly set forth in applicable Littelfuse documentation. Littelfuse shall not be liable for any claims or damages arising out of products used in applications not expressly intended by Littelfuse as set forth in applicable Littelfuse documentation. The sale and use of Littelfuse products is subject to Littelfuse Terms and Conditions of Sale, unless otherwise agreed by Littelfuse. "Littelfuse" includes Littelfuse, Inc., and all of its affiliate entities.

The Littelfuse models 111P (115 volt, ⅓ to 1hp); 233P-1.5 (230 volt, ⅓ to 1.5hp); and 233P (230 volt, ⅓ to 3hp) are single-phase pump monitors used in a variety of applications to protect from dry-well, dead-head, jammed impeller, rapid-cycling, overvoltage, and undervoltage conditions.

Operation
A calibration adjustment allows the unit to be calibrated to your specific pumping applications, which reduces the possibility of false or nuisance tripping. A unique microcontroller-based voltage and current-sensing circuit constantly monitor the incoming power for fluctuations, overcurrent, and undercurrent conditions. When an abnormality, such as loss of suction, is detected, the product deactivates its output relay and directly disconnects the pump motor. The relay then begins its user-selectable restart delay (dry-well recovery) timer. When the timer counts to zero or power is removed and reapplied, the relay reactivates its output relay and turns the pump back on. The infrared LED communicates with a hand-held diagnostics tool called the Informer* (sold separately). The Informer displays parameters including calibration points, trip points, run time and last faults.

There are special considerations for pump cables larger than #10 AWG: In some cases where larger motors are installed with deep-set pumps, pump cables are used that exceed the relay’s terminal size. In these conditions, a short splice of #10 AWG or #12 AWG may be a solution at the control box. Note: All local, state, and national electric codes should be followed when applying this solution.

Note: The description and operations apply to Littelfuse models 111P (115 V, ⅓ to 1 hp); 233P-1.5 (230 V, ⅓ to 1.5 hp); and 233P (230 V, ⅓ to 3 hp). These models have a sensitivity adjustment for the dry-well trip point. After calibration is complete, you can adjust the sensitivity for the dry-well/dead-head trip point from 70-90 % of the full load. This makes the unit even more adaptable to varying pumping applications. If you have a very low producing well, you increase the sensitivity closer to the 90 % mark, or if you have a very heavy producing well, you should decrease the sensitivity around the 70 % mark.

*Informer: A hand-held diagnostic tool that uses an infrared receiver to access information that can be helpful for troubleshooting the system.

Features

  • Proprietary microcontroller-based circuitry
  • Onboard calibration process
  • Onboard sensitivity adjustment

Access specifications, certifications, check availability and order parts below

Catalog #Input
Voltage (V)
Input Load Range (hp)Output
Form
Termination TypeMounting MethodDimensionsWeight (lbs/g)Overcurrent Trip ClassInput AC Line Frequency (Hz)Maximum Input PowerOutput Load Rating (VA)Overvoltage Trip Voltage (%)Rapid Cycle Timer (s)Restart Delay RangeTrip Delay RangeStockSamplesCompare
233P230 Vac1/3 - 3SPSTTorque: 13 in-lbs; Wire: Solid or stranded 10 - 22 AWG#8 screws2.93 H x 5.25 W x 2.91 D in. (73.7 x 133.4 x 74 mm)0 Kg125% of calibration point50 / 60 (50 will increase all delay timers by 20%)53 hp @ 240 Vac (17 A max.)265 Vac4 restarts allowed in 60 s periodOver/Under Voltage: 2 s; All other faults: Manual; 2 - 225 mOvercurrent: 5 s; Dry-well: 4 sCheckOrder
233P-1.5230 Vac1/3 - 1.5SPSTTorque: 13 in-lbs; Wire: Solid or stranded 10 - 22 AWG#8 screws2.93 H x 5.25 W x 2.91 D in. (73.7 x 133.4 x 74 mm)0 Kg125% of calibration point50 / 60 (50 will increase all delay timers by 20%)51.5 hp @ 240 Vac (10 A max.)265 Vac4 restarts allowed in 60 s periodOver/Under Voltage: 2 s; All other faults: Manual; 2 - 225 mOvercurrent: 5 s; Dry-well: 4 sCheckOrder
233P-1.5-ENCL230 Vac1/3 - 1.5SPSTTorque: 13 in-lbs; Wire: Solid or stranded 10 - 22 AWG#8 screws8.3 H x 5.36 W x 3.68 D in. (210.8 x 136.1 x 93.5 mm)0 Kg125% of calibration point50 / 60 (50 will increase all delay timers by 20%)51.5 hp @ 240 Vac (10 A max.)265 Vac4 restarts allowed in 60 s periodOver/Under Voltage: 2 s; All other faults: Manual; 2 - 225 mOvercurrent: 5 s; Dry-well: 4 sCheckOrder
233P-ENCL230 Vac1/3 - 3SPSTTorque: 13 in-lbs; Wire: Solid or stranded 10 - 22 AWG#8 screws8.3 H x 5.36 W x 3.68 D in. (210.8 x 136.1 x 93.5 mm)0 Kg125% of calibration point50 / 60 (50 will increase all delay timers by 20%)53 hp @ 240 Vac (17 A max.)265 Vac4 restarts allowed in 60 s periodOver/Under Voltage: 2 s; All other faults: Manual; 2 - 225 mOvercurrent: 5 s; Dry-well: 4 sCheckOrder
To request product environmental information, please complete the Product Environmental Information Request Form.