background-waves

FB120A

Product Status| Activei

FB120A

FLASHER FAILURE ALARM RELAY | Series: FB120A FB230A
info
The FB120A and FB230A are used to monitor the operation of one two-lamp incandescent beacon and one beacon flasher (or auxiliary module). The flasher and lamps are monitored by sensing the flow of current in the circuit. If the lamp(s) or the flasher fail to operate properly, a solid-state output and an isolated SPDT relay energize. When connected to a site monitoring system, this unit provides the remote beacon monitoring protection required by the FAA/FCC. On a multiple beacon structure, one unit is required for each two-lamp incandescent beacon (one unit per beacon for LED beacons).


Operation
If one lamp in an incandescent beacon fails, the relay and solid-state lamp failure outputs energize after 10s. If the flasher fails in the ON or OFF condition, the relay and the solid-state flasher failure output energizes after 6s. If both failures occur, all three outputs energize after their trip delays.
Note: If both incandescent lamps fail, all three outputs will energize. The relay and solid-state flasher failure output energizes after 6s, and the solid-state lamp failure output energizes after 10s.

PropertyValue
Input Voltage (V)
120 V ac
Output Form
3 total: 1 relay and 2 solid state
Trip Delay Range
Flasher failure: Fixed at 6 s; -0/+40; Lamp failure: Fixed at 10 s; -0/+40%
Output Load Rating (VA)
One isolated SPDT relay rated 5 A resistive; Two solid-state line voltage outputs rated 0.5 A steady and 5 A inrush
Dimensions
3.5 H x 2.5 W in. (88.9 x 63.5 mm)
Circuitry
Encapsulated
Indication
Lamp failure (Red): LED glows when one or both lamps fail; Flasher failure (Red): LED glows when the flasher fails
Input AC Line Frequency (Hz)
50/60
Input Tolerance (%)
±15%
Lamp Failure Detection
For two 620 W or 700 W lamps
Lamp Socket Voltage
±10%; 50/60 Hz
Mounting Method
Surface mount with two #6 (M3.5 x 0.6) screws
Operating Temperature Max (°C)
65
Operating Temperature Maximum Fahrenheit
149
Operating Temperature Minimum Celsius
-55
Operating Temperature Minimum Fahrenheit
-67
Storage Temperature Maximum Celsius
85
Storage Temperature Maximum Fahrenheit
185
Storage Temperature Minimum Celsius
-55
Storage Temperature Minimum Fahrenheit
-67
Termination Type
7 position barrier block for 20 AWG (0.5 mm²) to 14 AWG (2.5 mm²) wire

FB120A Resources

Showing 1 to 1 of 1 Total Results
Share
Part NumberPart DescriptionRoHSPb-FreeRoHS (2015/863/EU) CertificateREACH (SVHC's) DeclarationREACH (SVHC's)Halogen FreeIPC-Material Declaration
FB120AFLASHER FAILURE ALARM RELAY

If the product environmental information that you are looking for does not appear in this tab, please complete the Product Environmental Information Request Form.